山東電纜橋架:電纜橋架與支架如何連接?
電纜橋架及支架和引入或引出的金屬電纜導(dǎo)管必須接地或接零可靠,且必須符合下列規(guī)定:
Cable trays and brackets, as well as metal cable conduits introduced or led out, must be reliably grounded or grounded, and must comply with the following regulations:
1、金屬電纜橋架及其支架全長應(yīng)不少于2處與接地或接零干線相連接。
1. The total length of the metal cable tray and its bracket should not be less than 2 points connected to the grounding or neutral main line.
2、非鍍鋅電纜橋架間連接板的兩端跨接銅芯接地線,接地線小允許截面積不小于4平方毫米。

2. The two ends of the connecting plate between non galvanized cable trays are crossed with copper core grounding wires, and the minimum allowable cross-sectional area of the grounding wire is not less than 4 square millimeters.
3、鍍鋅電纜橋架間連板的兩不跨接接地線,但連接板兩端不少于2個(gè)有防松螺帽或防松墊圈的連接固定螺栓。
3. The two non bridging grounding wires between galvanized cable trays shall be connected, but there shall be no less than two connection fixing bolts with anti loosening nuts or washers at both ends of the connecting plate.
以上就是有關(guān):山東電纜橋架 的介紹,想了解更多的內(nèi)容請點(diǎn)擊:http://www.sdgwjzcl09.com 我們將會(huì)全心全意為您提供滿分服務(wù),歡迎您的來電!
The above is an introduction to Shandong cable tray. For more information, please click: http://www.sdgwjzcl09.com We will wholeheartedly provide you with full score service. Welcome to call us!
下一篇:濟(jì)南電纜橋架:防火橋架制作工藝材料及性能
相關(guān)文章 / Recommended news
- 山東電纜橋架線槽什么情況下設(shè)置和不設(shè)置跨接線的要求
- 全長大于30米的電纜橋架,中間增加與保護(hù)導(dǎo)體的連接怎么做?
- 山東電纜橋架的安裝要求
- 濟(jì)南電纜橋架內(nèi)電纜的固定應(yīng)符合相關(guān)標(biāo)準(zhǔn)規(guī)范的規(guī)定
- 地下室山東橋架安裝檢查驗(yàn)收標(biāo)準(zhǔn)、驗(yàn)收節(jié)點(diǎn)
- 濟(jì)南電纜橋架廠家:弱電工程電纜橋架如何施工才規(guī)范?
- 濟(jì)南電纜橋架安裝施工技術(shù)與管控手冊
- 山東電纜橋架:電力電纜常識(shí)性知識(shí)和電纜試驗(yàn)方法介紹
- 山東電纜橋架安裝施工要求及規(guī)范
- 濟(jì)南電纜橋架安裝施工要求及規(guī)范
濟(jì)南電纜橋架到底需不需要跨接
安裝橋架
安裝橋架
安裝橋架
防火橋架